直流接地故障查找仪
技术规范专用部分
目 录
直流接地故障查找仪标准技术规范使用说明 ································································································································ 3 一 通用部分 ··················································································································································································· 5 1 总则 ····························································································································································································· 5 2 技术要求 ····················································································································································································· 5 2.1 引用标准 ············································································································································································· 5 2.2 直流接地故障查找仪的要求 ·············································································································································· 4 2.3 安全要求 ············································································································································································· 5 2.4 标志、包装、运输、储存 ·················································································································································· 7 3 试验 ····························································································································································································· 7 4 现场安装服务、设计联络、工厂检验和监造、工厂(现场)验收 ······················································································· 8 4.1 现场安装服务 ··································································································································································· 14 4.2 设计联络会 ······································································································································································· 14 4.3 工厂检验和监造································································································································································ 14 4.4 工厂(现场)验收 ······························································································································································ 9 二 专用部分 ··················································································································································································· 9 1 标准技术参数 ············································································································································································· 9
一、通用部分
1 总则
1.1 本规范文件提出了直流接地故障查找仪的功能设计、结构、性能、安装等方面的技术要求。
1.2 本规范提出的是最低限度的要求,并未对一切技术细节作出规定,也未充分引述有关标准和规范的条文,供方应提供符合本规范和工业标准的优质产品。
1.3 投标人应具有备良好的财务状况和商业信誉。投标方应随同投标书提供所要求的资格证明文件及供货记录。
1.4 如果投标人没有以书面的形式对本规范的条文提出异议,则表示投标人提供的设备完全符合本规范的要求;如有与本规范要求不一致的地方,必须逐项在“项目单位技术差异表”中列出。如果没有不一致的地方,必须在“项目单位技术差异表”中写明为“无差异”。 1.5 本规范所使用的标准如遇与投标人所执行的标准不一致按较高的标准执行。 1.6 本规范将作为订货合同的附件,与合同具有同等的法律效力。本规范未尽事宜,由合同签约双方在合同谈判时协商确定。
1.7 供方职责。供方的工作范围将包括但不限于下列内容: 1.7.1 提供标书内所有设备及设计说明书及制造方面的说明。 1.7.2 提供设备安装、使用的说明书。
1.7.3 提供试验和检验的标准,包括试验报告和试验数据。
1.7.4 提供图纸,制造和质量保证过程的一览表以及标书规定的其他资料。 1.7.5 提供设备管理和运行所需有关资料。
1.7.6 所提供设备应发运到规定的目的地,并负责现场安装、调试。
1.7.7 如标准、规范与本规范的条文有明显的冲突,则供方应在制造设备前,用书面形式将冲突和解决办法告知需方,并经需方确认后,才能进行设备制造。
1.7.8 在更换所用的准则、标准、规程或修改设备技术数据时,供方有责任接受需方的选择。 2 技术要求 2.1 引用标准
下列标准所包含的条文,通过在本规范书中引用而构成本规范书的基本条文。在本规范出版时,所示版本均为有效。所有标准都会被修订,使用本规范的各方应探讨使用下列标准最新版本的可能性。
表1 技术规范引用标准
标准(文件)号 GB/T 191 GB/T 2423.1 GB/T 2423.2 GB/T 2423.5 GB/T 2423.6 GB/T 2423.10 GB/T 2900.1 GB/T 2900.17 GB/T 2900.32 GB/T 2900.33 标准(文件)名称 包装储运图示标志(GB/T 191-2008,ISO 780: MOD) 电工电子产品环境试验 第2部分:试验方法 试验A:低温(IEC 60068-2-1: IDT) 电工电子产品环境试验 第2部分:试验方法 试验B:高温(IEC 60068-2-2:2007,IDT) 电工电子产品环境试验 第2部分:试验方法 试验Ea和导则:冲击(idt IEC 60068-2-27:) 电工电子产品环境试验 第2部分:试验方法 试验Eb和导则:碰撞(idt IEC 60068-2-29:) 电工电子产品环境试验 第2部分:试验方法 试验Fc:振动(正弦)(IEC 60068-2-6: IDT) 电工术语 基本术语 电工术语 量度继电器 电工术语 电力半导体器件 电工术语 电力电子技术 (GB/T 2900.33,IEC 60050-551:,IEC 60050-551-20: IDT) GB 4208 GB/T 4365 GB/T 13384 GB/T 17626.2 GB/T 17626.3 GB/T 17626.4 GB/T 17626.5 GB/T 17626.6 GB/T 17626.8 GB/T 17626.10 GB/T 17626.12 GB/T 17626.29 GB/T 19826 GB/T 20626.1 GB/T 20626.2 GB/T 20626.3 DL /T856-2004 外壳防护等级(IP代码)(IEC 60529: IDT) 电工术语 电磁兼容(GB/T 4365-2003,idt IEC 60050(161):1990) 机电产品包装通用技术条件 电磁兼容 试验和测量技术 静电放电抗扰度试验(IEC 61000-4-2: IDT) 电磁兼容 试验和测量技术 射频电磁场辐射抗扰度试验(IEC 61000-4-3:,IDT) 电磁兼容 试验和测量技术 电快速瞬变脉冲群抗扰度试验(IEC 61000-4-4:,IDT) 电磁兼容 试验和测量技术 浪涌(冲击)抗扰度试验(IEC 61000-4-5:,IDT) 电磁兼容 试验和测量技术 射频场感应的传导骚扰抗扰度试验(IEC 61000-4-6: IDT) 电磁兼容 试验和测量技术 工频磁场抗扰度试验(IEC 61000-4-8:2001,IDT) 电磁兼容 试验和测量技术 阻尼振荡磁场抗扰度试验(idt IEC 61000-4-10) 电磁兼容 试验和测量技术 振荡波抗扰度试验(idt IEC 61000-4-12) 电磁兼容 试验和测量技术 直流电源输入端口电压暂降、短时中断和电压变化的抗扰度试验(IEC 61000-4-29: IDT) 电力工程直流电源设备通用技术条件及安全要求 特殊环境条件 高原电工电子产品 第1部分:通用技术要求 特殊环境条件 高原电工电子产品 第2部分:选型和检验规范 特殊环境条件 高原电工电子产品 第3部分:雷电、污秽、凝露的防护要求 2.2直流电源系统绝缘监测装置的要求 2.2.1使用条件要求
2.2.1.1正常使用环境条件
(1)设备运行期间周围空气温度不高于﹢45℃,不低于-10℃。
(2)日平均相对湿度不大于95%,月平均相对湿度不大于90%,且表面无凝露。 (3)海拔高度不超过2000m,大气压力范围为80~110kPa。 (4)安装使用地点无强烈振动和冲击,无强烈电磁干扰,外磁场感应强度均不超过0.5mT。 (5)安装垂直倾斜度不超过5%。
(6)使用地点没有爆炸危险介质,周围介质不含有腐蚀金属和破坏绝缘的有害气体及导电介质,没有霉菌存在。 2.3.1.2 正常使用电气条件
正常使用电气条件应符合表2的规定。
表2 正常使用电气条件
直流系统标称电压(V) 工作电压范围(V) 直流系统纹波系数 220 48~300 5% 2.3.2 安全性要求 2.3.2.1 直流接地故障查找仪检测信号电流大小:0—2mA可调。 2.3.3 结构与元器件要求 2.3.3.1 一般要求
(1)元器件应符合国家或行业现行相关标准的规定。
(2)应选用有产品合格证或质量合格证明文件的元器件,不得选用淘汰、落后的元器件。 2.3.3.2 外观
(1)面板上的元器件应采用以下方式合理布局:
a)产品正面应朝向巡视和操作者,面板上的按钮、开关、连接片等操作器件,以及各类声、光信号等指示器件应排列整齐、端正美观。
(2)用以说明面板上元器件功能的文字、符号、标志应正确、清晰、端正、耐久。 2.3.3.3 外壳
(1)产品的外壳应采用防锈蚀、防老化、防潮、阻燃,不产生有害气体,具有一定机械强度,不易变形的材料制作。
(2)产品的外壳应平整光滑,四周无突出异物。
(3)产品外壳的防护等级应不低于GB4208-2008中IP30的规定。 2.3.3.4 其他要求
(1)产品背面的端子和引线应选用阻燃型器件。
(2)产品背面应有保护接地端子,以及明显的接地标志。接地连接处有防锈、防粘漆措施,应能通过屏(柜)实现可靠接地。 2.3.4 检测功能要求
(1).系统对地电压测量功能,仪器可测量系统正对地电压,负对地电压,系统电压,可实现0—300V的电压监测范围;
(2).系统绝缘阻抗测量功能,仪器可测量系统正对地绝缘阻抗,负对地绝缘阻抗,可实现0—999KΩ的测量;
(3).交流串电检测功能,仪器可判断直流系统中的交流串电故障,并可测量直流系统中串入的交流电电压值,交流电压测量范围为0—280V;
(4).支路绝缘阻抗测量功能,仪器测量每条支路的正负对地绝缘阻抗大小; (5).支路接地故障点定位功能,仪器可实现接地故障支路接地故障点的定位功能; (6).电流表功能,装置可做高精度电流表使用,电流测量分辨率可达0.01mA; (7).具有不发信号接地查找功能,装置可以在不向系统注入任何信号的条件下实现接地故障点的定位;
(8).方向显示功能,对于测试出有接地指示的支路,仪器将会有方向指示箭头提示用户接地点与所查找接地点之间的相对方向,提高查找效率。
(9).绝缘指数分析功能,在使用接地功能检测时,检测完一条支路后,探测仪会显示该条支路的绝缘指数情况,供用户参考分析。
(10).波形曲线显示功能,在使用探测仪对被测支路绝缘状况进行检测时,显示屏会以波形曲线形式显示被测支路电流变化情况,方便使用者快速准确的实现故障点的查找。 2.3.5 交流窜电告警
产品应能显示窜入交流电压的幅值,并且能够准确找到接地点。 2.5 安全要求
2.5.1 电气绝缘性能
2.5.1.1 产品的下列部位应进行电气绝缘性能试验
a) 各独立电路与地(即金属框架)之间; b) 无电气联系的各电路之间。 2.5.1.2 绝缘电阻
用开路电压为表4规定电压测试仪器测量,2.5.1.1所列部位的绝缘电阻应不小于10MΩ。
2.5.1.3 介质强度
2.5.1.1所列部位,应能承受频率为50±5Hz的工频耐压试验,历时1min,(也可采用直流电压,试验电压为交流电压有效值的1.4倍)。试验等级见表3。 2.5.1.4 冲击耐压
2.5.1.1所列部位,应能承受标准雷电波的冲击耐压试验。试验电压值按表9选取。
表9 绝缘试验的试验等级
额定绝缘电压Ui(V) Ui≤63 63<Ui≤250 250<Ui≤500 绝缘电阻测试仪器的电压等级(V) 250 500 1000 介质强度试验电压(kV) 0.5(0.7) 2.0(2.8) 2.0(2.8) 冲击耐压试验电压(kV) 1 5.0 5.0 注1:括号内数据为直流介电强度试验值; 2:出厂试验时,介质强度试验允许试验电压高于表4中规定值的10%,试验时间为1s。 2.5.2 电磁兼容性能 2.5.2.1 静电放电抗扰度
设备应承受GB/T17626.2-2006中第五章规定的试验等级为3级静电放电抗扰度试验。 2.5.2.2 射频电磁场辐射抗扰度
设备应承受GB/T17626.3-2006中第五章规定的试验等级为3级射频电磁场辐射抗扰度试验。
2.5.2.3 电快速瞬变脉冲群抗扰度
设备应承受GB/T17626.4-2008中第五章规定的试验等级为3级的电快速瞬变脉冲群振荡波抗扰度试验。
2.5.2.4 浪涌(冲击) 抗扰度
设备应承受GB/T17626.5-2008中第五章规定的试验等级为4级的浪涌(冲击) 抗扰度试验。
2.5.2.5 射频场感应的传导骚扰抗扰度
设备应承受GB/T17626.6-2008中第五章规定试验等级为3级的射频场感应的传导骚扰抗扰度试验。
2.5.2.6 工频磁场抗扰度
设备应承受GB/T17626.8-2006中第五章规定试验等级为4级的工频磁场抗扰度试验。 2.5.2.7 阻尼振荡磁场抗扰度
设备应承受GB/T17626.10-1998中第五章规定试验等级为4级的阻尼振荡磁场抗扰度试验。
2.5.2.8 振荡波抗扰度
设备应承受GB/T17626.12-1998中第五章规定的试验等级为3级的1MHz和l00kHz振荡波抗扰度试验。
2.5.2.9 电源输入端口电压短时中断的抗扰度
设备应承受GB/T17626.29-2006中第五章规定的试验等级为0%UT,分别以2.3条设备工作电压范围的上限和下限作为试验等级基准UT,持续时间为0.3s的直流电源输入端口电压短时中断的抗扰度试验。 2.5.3 环境适应性 2.5.3.1 低温
设备应能承受GB/T 2423.1-2008中“试验Ad:散热试验样品温度渐变的低温试验——试验样品在温度开始稳定后通电”规定的,以2.3.1.1设备运行环境温度下限作为试验温度,持续时间为2h的低温试验。 2.5.3.2 高温
设备应能承受GB/T 2423.2-2008中“试验Bd:散热试验样品温度渐变的高温试验——试验样品在升温调节期不通电”规定的,以2.3.1.1设备运行环境温度上限作为试验温度,持续时间为2h的高温试验。 2.5.3.3 冲击
设备应能承受GB/T2423.5-1995中第五章规定的,在每个轴向上,峰值加速度为2
300m/s,标称脉冲持续时间为18ms,采用半正弦形脉冲波形的冲击试验。 2.5.3.4 碰撞
设备应能承受GB/T2423.6-1995中第五章规定的,在每个轴向上,峰值加速度为2
100m/s,标称脉冲持续时间为16ms,碰撞次数为1000次的碰撞试验。 2.5.3.5 振动(正弦) 2.5.3.5.1 振动响应检查
设备应能承受GB/T2423.10-2008中第五章规定的,在10Hz到150Hz范围内,在每个轴
2
向上,位移幅值为3.5mm或加速度幅值为10m/s的振动响应检查试验。 2.5.3.5.2 耐久试验
如果在振动响应检查中,在10Hz到150Hz的频率范围内出现机械共振或其他作用的响应,应进行定频耐久试验,否则进行扫频耐久试验。 (1)扫频耐久试验
设备应能承受GB/T2423.10-2008中第五章规定的,在每个轴向上进行20次的2.5.3.5.1规定的扫频循环。 (2)定频耐久试验
设备应能承受GB/T2423.10-2008中第五章规定的,在振动响应检查中在每一轴向上找到的每个危险频率上,进行持续时间为10min的振动耐久试验。 2.6 标志、包装、运输、储存 2.6.1 标志
2.6.1.1 每套产品必须有铭牌,应安装在明显位置,铭牌上应标明以下内容:
a)产品名称; b)产品型号;
c)额定工作电压 V; d)出厂编号; e)生产日期; f)制造厂名; g)适用标准。
2.6.1.2 产品外包装上应有清晰、耐久的包装贮运图示标志,图示标志应符合GB/T191的规定。
2.6.2 包装
产品包装应采取防潮、防振措施,符合GB/T13384的规定,产品随带文件及附件如下: a)装箱清单; b)出厂检验报告; c)合格证; d)使用说明书;
e)维修专用工具和必备配件。 2.6.3 贮运
2.6.3.1 产品在运输过程中应有专用包装箱和防护措施,不应剧烈震动、冲击、暴晒、雨淋和倾倒放置。
2.6.3.2 产品在贮存期间,应放置在空气流通,无腐蚀性和爆炸气体的仓库内。 3 试验
直流接地故障查找仪中所用元件均应按各自的产品标准进行型式试验、出厂试验和现场交接试验。现场交接试验可与用户协商进行。
直流接地故障查找仪的各主要部件应进行材料试验,以确认部件和材料是否有缺陷,并应检查部件的设计和结构是否满足本规范要求。
直流接地故障查找仪应在工厂进行全面检查以确保设备功能的完好性、适应性和满足本规范书及相关标准、规范的要求。
4 现场安装服务、设计联络、工厂检验和监造、工厂(现场)验收 4.1 现场安装服务 4.1.1 概述
4.1.1.1 卖方应指定一名工程技术人员配合买方的工作,对合同设备的安装、调试和现场试验等进行技术指导。买方应为卖方的现场派出人员提供工作和生活的便利条件。 4.1.1.2 卖方应派两名以上工程技术人员到现场,对合同设备进行现场安装、调试和试验。 4.1.1.3 卖方现场工作人员应听从买方现场技术人员的指挥和管理,确保现场施工安全,防止直流电源短路,防止误碰运行中的设备,防止造成运行设备断电,防止造成直流系统接地,防止人员触电。工作完毕,应清理现场,并将现场电缆沟、防火墙、屏柜防火封堵设施等恢复原样。
4.1.1.4 买卖双方应该根据施工的进展通过协商决定卖方现场派出人员的专业、人员数量、服务持续时间以及到达和离开工地的日期。 4.1.2 任务和责任
4.1.2.1 卖方指定的现场派出人员,应在合同范围内与买方充分合作与协商。双方的现场代表,无权变更和修改合同。
4.1.2.2 卖方现场派出人员应按合同规定完成有关设备的技术服务,完成设备的安装、调试和验收试验。
4.1.2.3 卖方现场派出人员应协助买方在现场对运行和维护的人员进行必要的培训。 4.1.2.4 卖方现场派出人员应满足买方对安装、调试工作提出的技术和质量方面的合理意见和建议。
4.2 设计联络会
4.2.1 为协调设计及其他方面的接口工作,根据需要买方与卖方应召开设计联络会。在签约后的30天内,卖方应向买方建议设计联络会方案。 4.2.2 设计联络会内容:
1) 复核并确认设备的主要性能和参数; 2) 检查质量保证程序及质控措施; 3) 确定装置要求/运输尺寸和质量,以及工程设计的各种接口的资料要求; 4) 讨论交货程序; 5) 讨论监造、工厂试验及检验问题; 6) 讨论调试及验收试验; 7) 买卖双方提出的其他内容。 4.2.3 双方应作好各次联络会议纪要,包括讨论的项目、内容和结论,经双方代表签字生
效。会议纪要与合同具有同等效力。 4.3 工厂检验和监造
买方有权派遣其检验人员到卖方及其分包商的车间场所,对合同设备的加工制造进行检验和监造。
监造人员参加工厂试验,包括会签任何试验结果,既不免除卖方按合同规定应负的责任,也不能代替合同设备到达买方后的检验。
监造人员有权前往卖方和(或)其分包商生产现场,观察和了解该合同设备工厂试验的情况及其运输包装的情况时,若发现任一货物的质量不符合合同规定的标准,或包装不满足
要求,监造人员有权发表意见,卖方应认真考虑其意见,并采取必要措施以确保合同设备的质量。
若买方不派或未按时派遣监造人员参加上述试验,卖方应在接到买方相关通知后,自行组织检验。
为对合同设备进行实地了解,卖方应在本厂内组织一次对买方的培训。 4.4 工厂(现场)验收
满足国家电网公司相关企业标准中关于工厂验收(现场验收)的规范。
二、专用部分
1 标准技术参数
投标人应认真逐项填写标准技术参数表(见表10)中投标人保证值,不能空格,对于“投标人保证值”栏中有“*”标志者不能以“响应”两字代替,不允许改动招标人要求值。如有差异,请填写表17投标人技术偏差表。
直流接地故障查找仪标准技术参数 1.使用环境
环境温度:-30℃~+50℃; 相对湿度:≤95%; 2.无线通信技术指标
信号功率:≤ 10dbm; 信号频段:433Mhz; 灵敏度:-106dBm;
传输距离:在视距情况下,离地2米可靠传输距离250米 3.分析仪技术指标
适用直流系统电压等级: 48V,110V,220V或用户指定电压等级 系统正负电压测量范围:0—300V 对地直流电压测量范围:0—300V 对地交流电压测量范围:0—300V 交流串电故障告警门限:5V 电压测量分辨率:0.1V
系统对地电阻测量范围:0—999.9KΩ 接地电阻测量分辨率:0.1KΩ 显示方式:LCD
检测信号电流大小:0—2mA可调 检测信号电压幅值:0—50V可调
信号频率:无信号模式与0.16Hz可选 抗直流系统分布电容干扰:1000uF 4.探测仪技术指标
信号模式下支路绝缘阻抗检测范围:
系统电压等级为220V: 0 -600KΩ 系统电压等级为110V: 0 -300KΩ 系统电压等级为48V: 0 -60KΩ 绝缘阻抗测量分辨率:0.1KΩ
无信号模式下支路绝缘阻抗检测范围: 系统电压等级为220V: 0 -50KΩ 系统电压等级为110V: 0 -25KΩ 系统电压等级为48V: 0 -10KΩ 绝缘阻抗测量分辨率:0.1KΩ 波形显示时间: 12秒 电流测量范围:±100mA 电流测量分辨率:0.01mA 显示方式:LCD
方向显示方式:同向或反向标示 抗直流系统支路分布电容干扰:100uF 与分析仪之间的使用距离:无距离限制 钳口大小:Ф30mm 日本万用直流传感器
1.分析仪1台
2.探测仪1台(配钳表) 3.五号电池4节 4.充电器1个 5.三芯电缆1根 6.说明书1本 7.合格证1份 8.保修卡1份 9.手提箱1个
因篇幅问题不能全部显示,请点此查看更多更全内容